I/P-E/P-D/P-P/I
Transducers

Model T5200
I/P, E/P
transducer

Flow Capacity: SFM (m3/H)* 0.15 (0.26)
Output Pressure:
PSIG (kPa)
3-15 (21-105)
Linearity - Independent:
% FS
± 0.25
Repeatability: % FS <0.1
Supply Pressure:
PSIG (kPa)
20 ± 2 (140 ± 14)
Underwriting Group Approvals:** F, C, E
Dimensions (Aprx):
Inches and (mm)
3 x 5 1/2 x 3 3/8
(76 x 138 x 85)

Model T522
I/P, E/P
transducer with booster

Flow Capacity: SFM (m3/H)* 15-45 (26-76)
Output Pressure:
PSIG (kPa)
Depends on ratio see catalog
Linearity - Independent:
% FS
Depends on ratio see catalog
Repeatability: % FS <0.1
Supply Pressure: PSIG (kPa) Depends on ratio see catalog
Underwriting Group Approvals:** F, C, E
Dimensions (Aprx):
Inches and (mm)
3 x 5 1/2 x 6
(76 x 138 x 150)

 

Model T5221
I/P, E/P
transducer with adjustable ratio relay

Flow Capacity: SFM (m3/H)* 40 (68)
Output Pressure:
PSIG (kPa)
0-150 (0-1050)
Linearity - Independent:
% FS
± 0.25
Repeatability: % FS <0.1
Supply Pressure: PSIG (kPa) 20 ± 2 (140 ± 14)
Relay 250 (1750)
Underwriting Group Approvals:** F, C, E
Dimensions (Aprx):
Inches and (mm)
7 3/8 x 10 1/2 x 4 7/8 (185 x 263 x 122)

Model T5400
Parallel digital to pneumatic
transducer with booster

Flow Capacity: SFM (m3/H)* 0.15 (0.26)
Output Pressure:
PSIG (kPa)
3-15 (21-105)
Linearity - Independent:
% FS
± 0.25
Repeatability: % FS -
Supply Pressure:
PSIG (kPa)
20 ± 2 (140 ± 14)
Underwriting Group Approvals:** -
Dimensions (Aprx):
Inches and (mm)
3 x 5 1/2 x 7 3/4
(76 x 138 x 119)

 

Model T542(*)
Parallel digital to pneumatic
transducer with booster

Flow Capacity: SFM (m3/H)* 0.15 (0.26)
Output Pressure:
PSIG (kPa)
Depends on ratio see catalog
Linearity - Independent:
% FS
Depends on ratio see catalog
Repeatability: % FS <0.1
Supply Pressure: PSIG (kPa) Depends on ratio see catalog
Underwriting Group Approvals:** -
Dimensions (Aprx):
Inches and (mm)
3 x 5 1/2 x 7 3/4
(76 x 138 x 194)

Model T5700
I/P, E/P
transducer

Flow Capacity: SFM (m3/H)* 17-47 (29-80)
Output Pressure:
PSIG (kPa)
3-15 (21-105)
Linearity - Independent:
% FS
± 0.5
Repeatability: % FS <0.1
Supply Pressure:
PSIG (kPa)
18-150 (126-1050)
Underwriting Group Approvals:** -
Dimensions (Aprx):
Inches and (mm)
Dia. 3 H 6 1/2
(Dia. 76 H 163)

 

 

Model T6000
Miniature I/P, E/P
modular transducer

Flow Capacity: SFM (m3/H)* 2.5 to 11 (4.25 to 19)
Output Pressure:
PSIG (kPa)
3-15 to 0-120
(21-105 to 0-840)
Linearity - Independent:% FS ± 0.5 to ± 1.0
Repeatability: % FS 0.25 to <0.1
Supply Pressure:
PSIG (kPa)
20-150 (140-1050)
Underwriting Group Approvals:** F,C,E
Dimensions (Aprx):
Inches and (mm)
1 1/2 x 2 1/4 x 3 3/4
(38 x 57 x 94)

Model T8000
Miniature 2-wire P/I
modular transducer

Flow Capacity: SFM (m3/H)* -
Output Pressure:
PSIG (kPa)
4-20 or 10-50mA
Linearity - Independent:% FS ± 0.1
Repeatability: % FS <0.1
Supply Pressure: PSIG (kPa) Inputs 0-120 (0-840) in 5 ranges
Underwriting Group Approvals:** F,C,E
Dimensions (Aprx):
Inches and (mm)
1 1/2 x 2 1/4 x 3 3/4
(38 x 57 x 94)

These pages are best viewed with or 3.0